472
Symbol Math Instructions Section 3-11
Description /(430) divides the signed binary (16 bit) values in Dd by those in Dr and out-
puts the result to R, R+1. The quotient is placed in R and the remainder in
R+1.
Flags
Precautions When the content of Dr is 0, an error will be generated and the Error Flag will
turn ON.
If as a result of the division, the content of R is 0000 hex, the Equals Flag will
turn ON.
If as a result of the division, the content of the leftmost bit of R is 1, the Nega-
tive Flag will turn ON.
Examples When CIO 000000 is ON in the following example, D00100 will be divided by
D00110 as 4-digit signed binary values and the quotient will be output to
D00120 and the remainder to D00121.
Index Registers ---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Area Dd Dr R
R +1 R
÷
Dd
Dr
Remainder
Quotient
(Signed binary)
(Signed binary)
(Signed binary)
Name Label Operation
Error Flag ER ON when the result is 0.
OFF in all other cases.
Equals Flag = ON when as a result of the division, R is 0.
OFF in all other cases.
Negative Flag N ON when the leftmost bit of the R is 1.
OFF in all other cases.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CJ - REFERENCE MANUAL 08-2008 and is the answer not in the manual?

Omron SYSMAC CJ - REFERENCE MANUAL 08-2008 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CJ - REFERENCE MANUAL 08-2008
CategoryController
LanguageEnglish

Related product manuals