Product Specifications
Samsung Electronics 2-17
Indoor Unit(cont.)
QCeiling type
Model AM056FNCDEH/TK AM071FNCDEH/TK
Power Supply ø/V/Hz 1/220~240/50 1/220~240/50
Mode*
1)
HP / HR HP / HR
Performance
Capacity
Cooling*
2)
kW 5.6 7.1
Btu/h 19,100 24,200
Heating*
3)
kW 6.3 8.0
Btu/h 21,400 27,200
Condensate (with High fan speed) Liters/h 2.87 2.87
Power
Input W 72/72 80/77
Running Current A 0.33/0.28 0.35/0.29
Sound Level Sound Pressure (Cooling / Heating)*
4)
dB(A) 45/45 47/47
Fan
Type - Sirocco Fan Sirocco Fan
Motor
Model - Y5S413B214 Y5S413B214
Type - Non Feedback SSR Non Feedback SSR
Output W *5) *5)
Airflow Rate
Cooling (High) m
3
/min 16.5 16.5
Heating (High) m
3
/min 20.0 20.0
Refrigerant
Type - R410A R410A
Control Method - EEV EEV
Temperature Control - Micom&Thermistors Micom&Thermistors
Safety Devices - Fuse Fuse
Piping
Connections
Liquid (Flare) ø, mm 6.35 9.52
Gas (Flare) ø, mm 12.7 15.88
Drain ø, mm VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Weight
Net Weight kg 21.0 21.0
Shipping Weight kg 25.5 25.5
Dimensions
Net Dimensions (W x H x D) mm 1000x650x200 1000x650x200
Shipping Dimensions (W x H x D) mm 1080x730x300 1080x730x300
Functions
Auto Restart - O O
Auto Swing - X X
Group/Individual Control - O O
External Contact Control - O O
Trouble Shooting by LED - X X
Standard
Accessories
Installation Manual - O O
Operation Manual - O O
Pattern Sheet for Installation - X X
Flexible Drain Hose - O O
Filter / Safety Grille - Filter (Washable) Filter (Washable)
Optional
Accessories
Wireless Remote Controller - AR-DH00 AR-DH00
Wired Remote
Controller
Simplified - MWR-WE10N MWR-WE10N
External Contact Interface Module - MIM-B14 MIM-B14
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB , Equivalent refrigerant piping : 7.5m , Level differences : 0m
*3) Norminal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB , Equivalent refrigerant piping : 7.5m , Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.