EasyManuals Logo

Samsung AM160FNBFGB/EU User Manual

Samsung AM160FNBFGB/EU
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #229 background imageLoading...
Page #229 background image
Troubleshooting
4-84 Samsung Electronics
2.
Cause of problem
4-4-40 Outdoor Cond Out sensor breakaway error
Yes
Yes
Is the Cond Out
sensor and the sensor holder correctly
attached?
Are there any changes
n the value of the sensor when operating from
stop to heating?
Is the Cond Out sensor
resistance value reasonable?
(Refer to E231)
Complete
Re-insert sensor.
Re-attach sensor holder.
Yes
1. Judgment Method
1) No inspection for Cooling operation.
2) For heating operation (Each of the conditions below needs to be satisfied for more than 20 minutes.)
High pressure average > 25kg/cm²OK
Low pressure average < 8.5kg/cm²OK
Teva, out - Tair , in3°C OK
Teva, in - Tair , in2°C OK
Tcond, out - Tair , out ≤ 0°C NO
Every compressor is in operation & indoor
unit operation and Thermo On OK
Error Content Outdoor Cond Out sensor breakaway error
No
Defective Sensor : Replace Sensor
No
Blocked Sensor Path :
Change heat exchanger Ass'y
No
×
(
Operation
)
(
Reservation
)
(
Blast
)
(
Filter
)
×
(
Defrost
)
 Outdoor Cond Out sensor breakaway/defective/ relevant path blocked.
Refer to the judgment method below.
Indoorunit display
Judgment Method
Cause of problem
Outdoor unit display

Table of Contents

Other manuals for Samsung AM160FNBFGB/EU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM160FNBFGB/EU and is the answer not in the manual?

Samsung AM160FNBFGB/EU Specifications

General IconGeneral
BrandSamsung
ModelAM160FNBFGB/EU
CategoryHeat Pump
LanguageEnglish

Related product manuals