Troubleshooting
4-108 Samsung Electronics
1. Judgment Method
Tini = Sump temperature when entering the CH operation delay condition
Tlast= Sump temperature when maintaining CH operation delay for two hours
Outside Air Temperature Sensor Value: Outside air temperature w
hen maintaining CH operation delay for two hours
TlastTini < 2°C
Tlast < Outside Air Temperature Sensor Value + 2°C
Outside Air Temperature Sensor Value < 30°C
If , and are satisfied at the same
time, then display E445.
Outdoor Unit Display
Indoor Unit Display
-
Judgment Method t3FGFSUPUIFKVEHNFOUNFUIPECFMPX
Special Cause t$$)$POOFDUPS1$#JTOPUDPOOFDUFE4VNQTFOTPSDPNQSFTTPSTFQBSBUFE0XOQSPCMFNPG$$)
No
Connect CCH connector to PCB.
Is the CCH connector connected to PCB?
Yes
No
Attach the sump sensor to the
lower part of the compressor.
Is the sump sensor attached
to the lower part of the compressor?
Yes
Yes
Does the E445 error occur even after
the outdoor unit power is put back in?
Yes
Change PCB.
No
Normal Operation
Is CCH resistance normal?
(500~700/infinite for disconnection)
No
Change CCH.
4-4-64 CCH Malfunction and Sump Sensor Miswiring Error

Table of Contents

Other manuals for Samsung AM160FNBFGB/EU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM160FNBFGB/EU and is the answer not in the manual?

Samsung AM160FNBFGB/EU Specifications

General IconGeneral
BrandSamsung
ModelAM160FNBFGB/EU
CategoryHeat Pump
LanguageEnglish

Related product manuals