Troubleshooting
4-106 Samsung Electronics
4-4-62
,
:
Prohibition of the operation of Compressor due to Ooutdoor Temperature
Indoor unit display
Cause of problem
No sign
t0QFSBUJPO1SPIJCJUJPONPEFCZUIFJOEPPSUFNQFSBUVSFMJNJU
Criteria
:
Right before an outdoor unit starts heating operation by On signal of an indoor Remocon, the
error occurs and prohibits the operation in outdoor temperature over 30°C
:
Right before operating heat refri gerant filling mode by the K1 switch of an out door PCB, the error
occurs and prohibits the operation in outdoor temperature over 15°C
Outdoor unit display
1. How to check
The above error code is not caused by a product's problem but a function to protect the product by limiting the available tempera-
ture
range so please refer to the usable temperature range in the product manual.
If the error code is displayed despite a condition that does not belong to any of the above
diagnosis methods, read the temperature
sensor value of the outdoor inlet air with View Mode or S-net, and if the actual outdoor temperature is different, please replace the
temperature sensor.
(prohibit heating operation in outdoor temperature over 30°C)
(prohibit heat filling operation in outdoor temperature over 15°C)

Table of Contents

Other manuals for Samsung AM160FNBFGB/EU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM160FNBFGB/EU and is the answer not in the manual?

Samsung AM160FNBFGB/EU Specifications

General IconGeneral
BrandSamsung
ModelAM160FNBFGB/EU
CategoryHeat Pump
LanguageEnglish

Related product manuals