Troubleshooting
4-86 Samsung Electronics
4-4-42 Constant Rate Compressor Discharge Temperature Sensor Error (OPEN/SHORT)
(Operation) ×(Reservation) (Blast) ×(Filter) ×(Defrost)
,
(Compressor 2, Compressor 3)
t$POTUBOUSBUFDPNQSFTTPSEJTDIBSHFUFNQFSBUVSFTFOTPS01&/4)035QSPCMFN
t3FGFSUPUIFJOTQFDUJPONFUIPECFMPX
Indoor Unit Display
Judgment Method
Special Cause
Outdoor Unit Display
1. Inspection Method
Did the connector for
the outdoor constant rate compressor discharge
temperature sensor break away
from the PCB?
Did the resistance value
significantly stray from the following
temperature tab
le?
Separate the connector for the outdoor constant
rate compressor discharge temperature sensor from
the PCB, and measure the resistance value between
the 2 terminals.
Restart operation after changing
PCB.
Restart operation after connecting
the connector to PCB
Change this part as it is the fault of
the constant rate compressor discharge
temperature sensor itself.
Yes
No
No
Yes
Temperature (°C)
130
120
100
80
60
25
20
10
0
Resistance (K)
8.9
11.2
18.5
32.0
59.0
200.0
242.0
362.0
553.0
Comp. 2 Comp. 3

Table of Contents

Other manuals for Samsung AM160FNBFGB/EU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM160FNBFGB/EU and is the answer not in the manual?

Samsung AM160FNBFGB/EU Specifications

General IconGeneral
BrandSamsung
ModelAM160FNBFGB/EU
CategoryHeat Pump
LanguageEnglish

Related product manuals