LOGO! Manual
A5E00067781 01
14
2.2.2 Connecting LOGO!’s Inputs
Prerequisites
Connect sensors to the inputs. The sensors may be push-
buttons, switches, photoelectric barriers, daylight control
switches etc.
Sensor attributesfor LOGO!
LOGO! 12/24 RC/RCo LOGO! 24
I1 ... I6 I7, I8 I1 ... I6 I7, I8
Circuit state 0 < 5 V DC < 5 V DC < 5 V DC < 5 V DC
Input current < 1.0 mA < 0.05 mA < 1.0 mA < 0.05 mA
Schaltzustand 1 > 8 V DC > 8 V DC > 8 V DC > 8 V DC
Input current > 1.5 mA > 0.1 mA > 1.5 mA > 0.1 mA
LOGO! 24
RC/RCo (AC)
LOGO! 230
RC/RCo
Circuit state 0 < 5 V AC < 40 V AC
Input current < 1.0 mA < 0.03 mA
Circuit state 1 > 12 V AC > 79 V AC
Input current > 2.5 mA > 0.08 mA
LOGO! 12
RCL
LOGO! 24
L
LOGO! 24
RCL...
LOGO! 230
RCL...
Circuit state 0 < 4 V DC < 5 V DC < 5 V DC < 40 V AC
Input current < 0.5 mA < 1.5 mA < 1.5 mA < 0.03 mA
Circuit state 1 > 8 V DC > 12 V DC > 12 V DC > 79 V AC
Input current > 1.5 mA > 4.5 mA > 4.5 mA > 0.08 mA
Installin
g
and Wirin
g
LOGO!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LOGO! 230RC and is the answer not in the manual?

Siemens LOGO! 230RC Specifications

General IconGeneral
Inputs8 digital inputs
Outputs4 relay outputs
Mounting TypeDIN rail
Protection TypeIP20
Dimensions90 x 72 x 55 mm
Output Current10 A
Operating Temperature0°C to 55°C
Power Supply115/230V AC
Storage Temperature-40°C to +70°C