75
LOGO! Manual
A5E00067781 01
Note
Always specify a time T 0.10 s. For T = 0.05 s and
T = 0.00 s the time T is not defined.
Accuracy of T
All electronic components have minute differences. This
can result in deviations in the set time (T). In LOGO! the
maximum deviation is 1 %.
Example:
In 1 hour (3600 seconds) the deviation is 1 % (i.e. 36 sec-
onds).
In 1 minute the deviation is therefore only 0.6 seconds.
Accuracy of the time switch
To make sure that this deviation doesn’t result in the clock
in C variants running inaccurately, the time switch is regu-
larly compared with a high-precision time base and ad-
justed accordingly.
This results in a maximum time error of 5s a day.
4.3.3 Clock Buffering
The internal clock of a LOGO! module continues to run if
there is a power failure, i.e. it has a power buffer. The dura-
tion of the reserve power is affected by the ambient tem-
perature. At an ambient temperature of 25°C the typical
power buffer is 80 hours.
4.3.4 Retentivity
The switching states and counter values can be kept reten-
tively in the special functions. To do this, retentivity must be
switched on for the relevant function.
LOGO! Functions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LOGO! 230RC and is the answer not in the manual?

Siemens LOGO! 230RC Specifications

General IconGeneral
Inputs8 digital inputs
Outputs4 relay outputs
Mounting TypeDIN rail
Protection TypeIP20
Dimensions90 x 72 x 55 mm
Output Current10 A
Operating Temperature0°C to 55°C
Power Supply115/230V AC
Storage Temperature-40°C to +70°C