Error Diagnosis
6-2
SIMATIC Rack PC IL 40 SManual
A5E00200171-01
6.1 Problems When Using Modules from Other
Manufacturers
Error Display
The PC crashes during power up.
Cause
The following causes are possible:
Double assignment of I/O addresses
Double assignment of hardware interrupts and/or DMA channels
Signal frequencies or signal levels are not met
Different connector assignments
”Reset Configuration” was not carried out.
Remedy
Check your computer configuration:
If the computer configuration is the same as when your PC was delivered,
please contact your technical support team.
If the computer configuration has changed, reestablish the configuration you
had when your PC was delivered. Remove any modules from other
manufacturers. Perform a complete restart on your PC.
If the PC still crashes, you must contact your technical support team.
If the error no longer occurs, the module you used from another
manufacturer was the cause of the fault. Replace this module with a
Siemens module, or contact the module supplier.
Force ”Reset Configuration” via BIOS Setup (see Manual BIOS Setup” on the
CD supplied “Rack PC IL 40 S Documentation and Drivers”.

Table of Contents

Other manuals for Siemens Simatic series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic series and is the answer not in the manual?

Siemens Simatic series Specifications

General IconGeneral
BrandSiemens
ModelSimatic series
CategoryIndustrial PC
LanguageEnglish

Related product manuals