8   System Decommissioning
8.1   Disconnecting Inverter
CAUTION
Danger of burns!
Even if the inverter is shut down, it may still be hot and cause burns. Wear protective
gloves before operating the inverter after it cools down.
For maintenance or other service work, the inverter must be switched off.
Proceed as follows to disconnect the inverter from the AC and DC power sources. Lethal
voltages or damage to the inverter will follow if otherwise.
step 1 Disconnect the external AC circuit breaker and prevent it from inadvertent reconnection
step 2 Rotate the DC switch to the "OFF" position for disconnecting all of the PV string inputs.
step 3 Wait about 5 minutes until the capacitors inside the inverter completely discharge.
step 4 Ensure that the DC cable is current-free with a current clamp.
- - End
8.2   Dismantling the Inverter
CAUTION
Risk of burn injuries and electric shock!
After the inverter is powered off for 5 minutes, measure the voltage and current with
professional instrument. Only when there is no voltage nor current can operators who
wear protective equipment operate and maintain the inverter.
107

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG125CX-P2 and is the answer not in the manual?

Sungrow SG125CX-P2 Specifications

General IconGeneral
Max. DC Voltage1100 V
Rated AC Power125 kW
Max. DC Power150 kW
Start-up Voltage200 V
MPPT Voltage Range200 V - 1000 V
Max. Short-circuit Current per MPPT40 A
Max. AC Power137.5 kW
Max. AC Current198 A
Rated AC Voltage400 V
Rated Grid Frequency50/60 Hz
Total Harmonic Distortion<3%
Power Factor Adjustment Range0.8 leading to 0.8 lagging
DC Connection TypeMC4
Protection ClassIP66
Maximum DC Input Power150 kW
DC Inputs per MPPT2
Cooling MethodSmart forced air cooling
Operating Temperature Range-25°C to +60°C
Humidity Range0 - 100%
CommunicationRS485, Ethernet