User Manual 5 Electrical Connection
5.6.4 Connection Procedure (For a single-core cable)
step 1 Disconnect the AC-side circuit breaker and prevent it from inadvertent reconnection.
step 2 Loosen two screws on the front cover of the junction box using the supplied hexagon socket wrench,
andopen the junction box.Keep the cover of the junction box open during wiring with a limit rod
attached to the cover.
The screws on the front cover are captive screws. When the front cover is opened, the
screws remain on it.
step 3
Loosen screws on the bottom sealing plate using the supplied hexagon socket wrench, and remove
the sealing plate.
53

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG125CX-P2 and is the answer not in the manual?

Sungrow SG125CX-P2 Specifications

General IconGeneral
Max. DC Voltage1100 V
Rated AC Power125 kW
Max. DC Power150 kW
Start-up Voltage200 V
MPPT Voltage Range200 V - 1000 V
Max. Short-circuit Current per MPPT40 A
Max. AC Power137.5 kW
Max. AC Current198 A
Rated AC Voltage400 V
Rated Grid Frequency50/60 Hz
Total Harmonic Distortion<3%
Power Factor Adjustment Range0.8 leading to 0.8 lagging
DC Connection TypeMC4
Protection ClassIP66
Maximum DC Input Power150 kW
DC Inputs per MPPT2
Cooling MethodSmart forced air cooling
Operating Temperature Range-25°C to +60°C
Humidity Range0 - 100%
CommunicationRS485, Ethernet