User Manual 5 Electrical Connection
NOTICE
After being crimped, the OT terminal must wrap the wires completely, and the wires
must contact the OT terminal closely.
When using a heat gun, protect the device from being scorched.
Keep the PV+ cable and PV– cable close to each other when connecting DC input
cables.
Before connecting a power cable (such as the AC cable, the DC cable, etc.), confirm
that the label and identifier on the power cable are correct.
When laying out communication cables, separate them from power cables and
keep them away from strong interference sources to prevent communication in
terruption.
All vacant terminals must be covered with waterproof covers to prevent affecting
the protection performance.
Ensure that AC output cables are firmly connected. Failing to do so may cause
inverter malfunction or damage to its AC connectors.
When the wiring is completed, seal the gap at the cable inlet and outlet holes with
fireproof/waterproof materials such as fireproof mud to prevent foreign matter or
moisture from entering and affecting the long-term normal operation of the invert
er.
The cable colors in figures in this manual are for reference only. Please select cables
according to local cable standards.
5.2   Terminal Description
All electrical terminals are located at the side and bottom of the inverter.
37

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG125CX-P2 and is the answer not in the manual?

Sungrow SG125CX-P2 Specifications

General IconGeneral
Max. DC Voltage1100 V
Rated AC Power125 kW
Max. DC Power150 kW
Start-up Voltage200 V
MPPT Voltage Range200 V - 1000 V
Max. Short-circuit Current per MPPT40 A
Max. AC Power137.5 kW
Max. AC Current198 A
Rated AC Voltage400 V
Rated Grid Frequency50/60 Hz
Total Harmonic Distortion<3%
Power Factor Adjustment Range0.8 leading to 0.8 lagging
DC Connection TypeMC4
Protection ClassIP66
Maximum DC Input Power150 kW
DC Inputs per MPPT2
Cooling MethodSmart forced air cooling
Operating Temperature Range-25°C to +60°C
Humidity Range0 - 100%
CommunicationRS485, Ethernet