10 Operation of LCD Display User Manual
78
10.10 Running Parameters Setting
10.10.1 Main Menu of Run-param
Main Screen(Press ENTER )→Menu screen(Press j×3)→Set-param(Press
ENTER)→Enter password(Press ENTER, Press j)→Run-param(Press ENTER)
On the “Run-param” screen, Press j to move arrow to
one item and Press ENTER to start this item setting.
For each item setting, Press h to move cursor right and
Press j to set the appropriate value.
Confirm by Pressing ENTER.
Tab. 10-4 Specification of Running Parameters
Parameter Explanation Default Range
Standby
time
The time from inverter initialization to
inverter feeding power to grid.
20s 20…255s
Recover
time
The time from the fault is cleared to
inverter feeding power to grid.
30s
[IT: 300s]
0…900s
P-W limits Inverter active power limits. 100.0% 0...100%
Q-Var
switch
Whether to start inverter reactive
power adjustment function.
[Pf]
[Pf] / [Qt] / [Off]
/ [Q(P)] / [Q(U)]
PF Power factor +1.000
-1.000…-0.800 /
+0.800…+1.000
Q-Var limits Inverter reactive power limits 0.0%
0...+100% /
0…-100%