Unintended use and misuse – inappropriate applications for the machine |
11
• Offices
• teaching rooms
• hotels
• shops
• homes and similar comfort zones
H Unintended use and misuse – inappropriate applications for the machine
Units for outdoor installation must be specified and ordered for outdoor installation. The units must not be used in envi-
ronments that exceed corrosion class C4 according to EN ISO 12944-2, and for transport of solid particles.
Examples of not intended use:
• Kitchen extraction
• swimming pools
• off-shore
• Ex-areas
• drying of washed clothes.
• Do not use the unit with partly finished duct systems.
• Do not use the unit for ventilation of the building site until the unit is properly provided with guards.
H.1 Air handling unit in operation
The pressure difference between interior and exterior of the unit must not exceed 2000 Pa for the Geniox 10 and up to
Geniox 31 (including Geniox 31), and 1500 Pa for Geniox 36 and Geniox 44.
Before start-up of the unit all ducts, safety guards and all protective devices must be mounted to prevent any access to
rotating fan impellers. All inspection doors must be closed and locked when the unit is in operation.
Do not use the unit without filters.
I Instructions for unloading on the site as well as installation and connection
I.1 Unloading on the site
The air handling unit – AHU - is delivered as one section or in several sections, which are to be assembled on site. The
AHU is delivered on transport pallets, legs or on a base frame. Loading and unloading as well as transport on the site is
possible by fork-lift truck or by crane using suitable lifting straps.
I.1.1 Unloading by fork-lift truck
The forks of the truck must be sufficiently long to avoid any damage to the AHU underside.
output |