Information about the residual risks |
39
Dangerous incident:
Persons touching conductive parts get electric shock, burns, heart flicker and so on.
Claim for reduction of danger:
By installation or repairs of conductive components, the shaft must be blocked to prevent any rotation.
L.1.7.3 Risk of rotating impeller caused by stack effect (chimney effect).
Hazards/dangerous area:
On special occasions stack effect also called chimney effect in the ducts create airflows that drives the impellers
by turned off motors.
Dangerous incident:
Injury of fingers, hands and arms.
Claim for reduction of danger:
Eliminate this airflow for supply air and exhaust air by dampers with spring return motors for automatic closing of
the dampers by turned off fan motors and by power failure.
L.1.8 Batteries for heating
L.1.8.1 Extreme temperatures - heating
Hazards/dangerous area:
Electrical heating elements can achieve surface temperature of 500 degree Celsius.
Batteries and pipes for hot water can achieve 95 degree Celsius.
Dangerous incident:
According to ISO 13732-1:2006, here is no direct risk of burns. (short-time contact lesser than 2,5 sec).
Claim for reduction of danger:
No.
L.1.8.2 Extreme temperatures - cooling
Hazards/dangerous area:
Evaporator batteries and pipes connected to cooling compressor can achieve minus 10 degrees Celsius.
Dangerous incident:
According to ISO 13732-1:2006, here is no direct risk of burns. (short-time contact lesser than 2,5 sec).
Claim for reduction of danger:
No.
L.1.9 Heat pump units
L.1.9.1 Risk of high temperature
Hazards/dangerous area:
Condenser batteries and pipes can achieve temperature of 60 degree Celsius.
Dangerous incident:
Vurderet ud fra ISO 13732-1:2006, der er umiddelbart ikke risiko for forbrændinger. (berøringstid 2,5 sek).
Claim for reduction of danger:
No
output |

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Geniox 12 and is the answer not in the manual?

SystemAir Geniox 12 Specifications

General IconGeneral
BrandSystemAir
ModelGeniox 12
CategoryAir Handlers
LanguageEnglish

Related product manuals