9-1
| Speed control for rotor and assembly of divided rotor
Annex 9 Speed control for rotor and assembly of divided rotor
9.1 Speed control
The cabinet with the speed control system for the rotor is installed behind the inspection door in the rotor section.
The cabinet contains the speed controller with all components, terminal blocks, LED displaying the operation mode, the
dual position DIP switch with 8 sliding levers for programming the rotor motor signal and a button for the activation of
the test mode.
Through the different combinations of the 8 sliding levers of this dual position DIP switch, the correct signal is available
for the 3 different motors used for the 12 sizes of air handling units. The sliding levers are set and the function is
checked at the factory. The positions of the levers appear from the tables below.
9.1.1 Selection of correct signal via the 8DIP switch levers
Position Function
Code
Up Active = ON 1
Down
Deactivated = OFF
0
The factory sets the positions of the 8 DIP switch levers for the maximum of 12 revolutions per minute for standard
temperature exchangers and for sorption-hybrid exchangers. The position of each of the 4 DIP switches to the left is
shown below.
Geniox
Pulley Position for DIP switches to the left
Motor
10 54 0000 90TYD-S214-M 2.8Nm
11 54 0000
12 54 1000
14 77 0000
16 77 1000
18 77 1000
20 85 0100 120TYD-S214-M 5.5Nm
22 95 0100
24 106 0100
27 118 0100
29 112 1100
31 112 1100
The factory sets the positions of the 8 DIP switch levers for the maximum of 20 revolutions per minute for sorption
exchangers. The position of each of the 4 DIP switches to the left is shown below.
Geniox
Pulley Position for DIP switches to the left
Motor
10 70 1000 90TYD-S214-M
11 77 1000
12 95 1000
14 95 1000
16 118 0100 120TYD-S214-M
18 112 1100
20 118 1100
22 132 1100
24 132 0110
27 160 1010
29 160 0110
31 150 0110
output |