Connection of fan motor and set-up manual for frequency converter |
12-1
Annex 12 Connection of fan motor and set-up manual for frequency converter
12.1 Connection of fan motor
Delta connection is shown to the left, and star connection is shown to the right.
12.2 Set-up for Danfoss FC101 for Geniox-units with AC motors
SETUP IS DONE IN FACTORY BEFORE DELIVERY
To reload Systemair factory settings from the control panel:
0-50: LCP Copy: [2]
Systemair factory set-up is based on Danfoss initialization.
14-22: Operation mode: [2] Initialisation (Danfoss Initialisation)
Turn power off and on.
Systemair factory set-up:
0-01: Language selection:
1-03: Torque characteristic: Single fan: [3] Auto-Energy optim.
With twin fan set-up: [1] Variable Torque
1-20: Motor Power: According to motor plate / order papers
With twin fan set-up total power must be used
1-24: Motor Current: According to motor plate / order papers
With twin fan set-up total current must be used
1-25: Motor Nominal Speed: According to motor plate / order papers
1-42: Motor Cable Length: 3m
1-50: Motor Magnetisation at zero speed.: 0 %
1-52: Min. Speed Normal Magnetisation: 10 Hz
1-73: Flying Start: [0] Disabled
1-90: Motor Thermal Protection: [2] Thermistor trip
3-15: Reference 1 Source: [2] Analog input AI54
1-93: Thermistor Source: [1] Analog input AI53
3-03: Maximum Reference: Max. Hz from order papers
3-16 + 3-17: Reference 2- and 3 Source: [0] No function
3-41 + 342: Ramp 1 up and down: 20 Sec.
4-19: Max. Output Frequency: 90Hz
4-14: Motor Speed High Limit: 90Hz
4-18: Current limit: 100 %
5-12: Terminal 27 Digital input: [0] No operation
5-40.0: Function Relay: [3] Drive ready/remote
5-40.1: Function Relay: [3] Drive ready/remote
6-25: Terminal 54 High Reference: Max. Hz from order papers
14-03: Over modulation: [1] Active
14-20: Reset Mode: [2] Automatic reset x 2
output |

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Geniox 12 and is the answer not in the manual?

SystemAir Geniox 12 Specifications

General IconGeneral
BrandSystemAir
ModelGeniox 12
CategoryAir Handlers
LanguageEnglish

Related product manuals