PROBLEM PROBABLE CAUSE SOLUTION
The Delivery Prompts are
incorrect
Customer ID opons have
not be congured
1. Determine what quesons must be asked and enter into Cus-
tomer ID 1 to 4 text.
2. If queson does not show, make sure the Request is enabled.
3. To make sure operator enters data into Customer ID 1 to 4,
make sure Enforce is Enabled.
4. Validaon only works if a Database has been loaded. Contact
TCS for further support.
Display Precision is incor-
rect
Precision changed for cali-
braon
1. There are two places to change display precision:
2. W&M Sengs under System Metrics
3. System Sengs under Delivery Sengs
Delivery ends during fuel-
ing
Delivery Timed Out Under Delivery Sengs, you must extend your Time Out seng from
180 or 600 seconds.
External Display is not
reading
Red Lion or Tekkino Serial
Display sengs are not
Enabled
1. Go to Auxiliary Devices and Enable External Display.
2. Choose what is to be displayed under Congure
3. Pulse driven displays from Red Lion must be congured correct.
Contact Red Lion for support.
I lost my passwords Passwords are not stored
locally
Contact TCS for factory support.
SYSTEM SETTINGS TROUBLESHOOTING (CONTINUED)
PROBLEM PROBABLE CAUSE SOLUTION
Product has wrong Name The Register was never
calibrated
Go into W&M Sengs and select product to change name or add new
product, then calibrate the product.
Metered volume not the
same as Delivered Volume
Product calibraon factor
was not properly entered
for 2
nd
product.
1. Under W&M Sengs, read Product 1001 calibraon factor and
copy it to Product 1002 under Edit Product Calibraon.
2. Entering calibraon factors under Product Parameters will require
a physical calibraon operaon.
When Product with Addi-
ve Pump is selected, I do
not see or hear the Injector
actuang.
Addive Injector Pump is
not Enabled for Product
Injector Pump not primed
or has leak
1. Go to Product Parameters of Product with the enabled Injector
Pump, then make sure Addive Injector is on External or Piston.
2. Check that pump wiring is terminated correctly on Pump Starter
and not reading 9V. If reading 0 or 12V, check the solenoid coil on
the Injector Pump.
3. Look for leaking ng on sucon side of Injector Pump.
4. Prime Injector Pump
Ticket is not set up correct-
ly
Ticket must be congured 1. Go to Accounng and select Congure Ticket
2. Adjust Ticket conguraon by adding, removing or eding each
line. See cket setup in the TCS User’s Guide for more infor-
maon.
Customer contact infor-
maon is missing from
cket
Customer contact infor-
maon is not setup in
Header or Footer
1. Go to Accounng and select Congure Ticket.
2. Header and Footer Defaults for customer contact informaon or
messages can be entered here.
Delivery cket will not
print
Out of paper or printer not
connected
Missing Minimum Ticket
1. Load paper cket and press Print.
2. Check cable connecon and terminaon of printer wiring for loose
connecon.
3. Check for worn cable throughout chassis.
4. Missing “Minimum” Ticket. Requires a copy from Exisng Ticket
and named Minimum.
WEIGHTS & MEASURES SETTINGS TROUBLESHOOTING