BAS-SVX50F-EN 15
Installing the Tracer TD7 Display
Installing the TD7 Display onto a VESA Mounting Bracket
The Tracer TD7 can be mounted near the UC600 with the supplied Ethernet cable and power cable,
or remotely mounted up to 328 ft (100 m.) by using a field-suppled 75 mm VESA mount.
Remote mounting requires the
following additional field-su
pplied components:
• A power source that will supply 24 VAC to the display
• E
thernet cable
• Power cables
Many commercial 75mm VESA mounti
ng brackets are available, which range from a simple wall
mount to tilt-and-swivel mounts (shown in Figure 4) or the TD7 Display Low Profile Mounting
Bracket (VESA 75mm, part number X05010511010).
Note: M
ounting Bracket X05010511010 is not supplied and mu
st be ordered separately from Trane.
14. Disconnect power at the circuit breaker and perform lockout/tagout procedures.
15. Disconnect the 24 VAC power from the UC600.
16. Mount the VESA mounting bracket according to manufacturer’s instructions.
17. Position the TD7 display
1onto the VESA mounting bracket 2 and align the four mounting
holes with the bracket while inserting and hand-tightening the four M-4 screws. (Some brands
of VESA mounting brackets may require the use of the four spacer washers to allow the M-4
screws to tighten properly.)
18. Securely tighten the M-4 screws
usin
g a Phillips screwdriver.
19. Follow steps 7 through 13
of “Installing the TD7 Display in a Trane Large Enclosure”to complete
this process.