Page #51 background imageLoading...
Page #51 background image
BAS-SVX50F-EN 51
Settings
Setting Up and Maintaining Schedules
Tracer TD7 supports three types of schedules: analog, binary, and multistate. A maximum of three
schedules can be created. Each schedule can contain up to 10 members, 10 events, and 25
exceptions.
Schedules are created on a series of “events” that occur on each
day of the week
. An event is a
change in a value at a specific time that can occur during any day of the week.
Each day is independent of the o
thers
and always begins with the schedule default value. The
schedule default value is applied to each day of the week and is the value that the schedule defaults
to at 12:00 a.m. for any given day.
Note: Scheduling
requires installation of UC600 version 3.0 or higher firmware.
Creating a Schedule
1. Navigate to the Settings screen, then touch the Schedules button.
2. Under Inactive Schedules, tou
ch a schedule (Figure 44).
Figure 44. Schedules screen (no active schedules)
3. Touch the Edit Schedu
le button (Figure 45, p. 52), then touch the Edit Members button.

Table of Contents

Other manuals for Trane Tracer TD7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer TD7 and is the answer not in the manual?

Trane Tracer TD7 Specifications

General IconGeneral
BrandTrane
ModelTracer TD7
CategoryController
LanguageEnglish

Related product manuals