B.4 Defaults by Drive Model and Duty Rating
ND/HD
Table B.3 Single-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Settings
No. Description Unit Default Settings
− Model − BA0001 BA0002 BA0003
o2-04 Drive Model Selection Hex 30 31 32
C6-01 Normal/Heavy Duty −
HD ND HD ND HD ND
0 1 0 1 0 1
− Motor rated power kW 0.1 0.18 0.25 0.37 0.55 0.75
C6-02 Carrier frequency − 4 7 4 7 4 7
E2-01 Motor rated current A 0.60 1.10 1.10 1.90 1.90 3.30
E2-02 Motor rated slip Hz 2.50 2.60 2.60 2.90 2.90 2.50
E2-03 Motor no-load current A 0.40 0.80 0.80 1.20 1.20 1.80
E2-05 Motor line-to-line resistance Ω
35.98 20.56 20.56 9.84 9.842 5.156
−
Momentary power loss ride-
through time
s 0.1 0.1 0.1 0.1 0.1 0.1
−
Mom. power loss Baseblock
time
s 0.2 0.2 0.2 0.2 0.2 0.3
No. Description Unit Default Settings
− Model − BA0006 BA0010
o2-04 Drive Model Selection Hex 33 34
C6-01 Normal/Heavy Duty −
HD ND HD ND
0 1 0 1
C6-02 Carrier frequency − 4 7 3 7
E2-01 Motor rated current A 3.30 6.20 6.20 8.50
E2-02 Motor rated slip Hz 2.50 2.60 2.60 2.90
E2-03 Motor no-load current A 1.80 2.80 2.80 3.00
E2-05 Motor line-to-line resistance Ω 5.156 1.997 1.997 1.601
− Momentary power loss ride-through time s 0.2 0.2 0.3 0.3
− Momentary power loss Baseblock time s 0.3 0.4 0.4 0.5
B.4 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual
247
B
Parameter List