EasyManuals Logo

York YVWA User Manual

York YVWA
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #131 background imageLoading...
Page #131 background image
JOHNSON CONTROLS
131
FORM 201.30-ICOM1 (519)
ISSUE DATE: 05/22/2019
7
SECTION 7 - MAINTENANCE
GENERAL REQUIREMENTS
The maintenance requirements for YVWA chillers are
shown below. The procedure is in the left-hand column
and the required frequency is marked with an X in the
right-hand column. Refer to the notes at the bottom of
the table to maintain warranty validation.
TABLE 43 - OPERATION/INSPECTION /MAINTENANCE REQUIREMENTS FOR YVWA CHILLERS
PROCEDURE DAILY WEEKLY MONTHLY ANNUALLY
Record operating conditions (on applicable log form) X
Check oil level in oil level sight glass X
Check refrigerant levels X
Check oil return system operation X
Check operation of motor starter X
Check oil heater operation X
Check 3-phase voltage and current balance X
Check programmable operating setpoints and safety
cutouts. Make sure they are correct for the application.
X
Verify condenser and evaporator liquid ows X
Check and repair leaks as needed¹ X
Check and tighten all electrical connections X
Check the motor windings resistance X
Clean or back ush VSD heat exchanger X¹
Replace VSD coolant (after cleaning heat exchanger) X
Perform oil analysis on compressor lube oil X¹
Perform refrigerant analysis X
Perform Eddy current testing and inspect tubes
Clean evaporator and condenser tubes
For operating and maintenance requirements listed above, refer to appropriate service literature, or contact a local Johnson Controls Field
Service Ofce.
¹ This procedure must be performed at the specied time interval by an industry certied technician, who has been trained and qualied to
work on this type of YORK equipment. A record of this procedure being successfully carried out must be maintained on le by the equipment
owner should proof of adequate maintenance be required at a later date for warranty validation purposes.
² More frequent service may be required, depending on local operating conditions or relaxed with good engineering controls (water quality).
Compressor vibration analysis is not prescribed. Due
to the compressor design, a typical vibration analysis
can be misleading.
Periodic oil filter changes are not recommended.
Change the oil, filter, and filter driers only when an oil
analysis indicates a moisture issue.

Table of Contents

Other manuals for York YVWA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YVWA and is the answer not in the manual?

York YVWA Specifications

General IconGeneral
BrandYork
ModelYVWA
CategoryChiller
LanguageEnglish

Related product manuals