ACS550 User’s Manual 109
Start-Up
Group 32: Supervision
This group defines supervision for up to three signals from Group 01, Operating
Data. Supervision monitors a specified parameter and energizes a relay output if the
parameter passes a defined limit. Use Group 14, Relay Outputs, to define the relay
and whether the relay activates when the signal is too low or too high.
Code Description
3201 SUPERV 1 PARAM
Selects the first supervised parameter.
Must be a parameter number from Group 01 Operating
Data.
If the supervised parameter passes a limit, a relay output is
energized.
The supervision limits are defined in this group.
The relay outputs are defined in Group 14 Relay Outputs
(definition also specifies which supervision limit is
monitored).
LO HI
Operating data supervision using relay outputs, when LOHI.
Case A = Parameter 1401
RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is SUPRV1 OVER or SUPRV 2 OVER.
Use for monitoring when/if the supervised signal exceeds a
given limit. The relay remains active until the supervised
value drops below the low limit.
Case B = Parameter 1401 RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is SUPRV 1 UNDER or SUPRV 2 UNDER.
Use for monitoring when/if the supervised signal falls
below a given limit. The relay remains active until the
supervised value rises above the high limit.
LO > HI
Operating data supervision using relay outputs, when LO>HI.
The lowest limit (
HI 3203) is active initially, and remains
active until the supervised parameter goes above the highest
limit (LO 3202), making that limit the active limit. That limit
remains active until the supervised parameter goes below
the lowest limit (HI 3203), making that limit active.
Case A = Parameter 1401
RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is SUPRV1 OVER or SUPRV2 OVER.
Initially the relay is de-energized. It is energized whenever
the supervised parameter goes above the active limit.
Case B = Parameter 1402
RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is SUPRV1 UNDER or SUPRV2 UNDER.
Initially the relay is energized. It is de-energized whenever
the supervised parameter goes below the active limit.
LO HI
Note! Case LO HI represents a normal hysteresis.
LO > HI
Note! Case LO>HI represents a special hysteresis with
two separate supervision limits.
3202 SUPERV 1 LIM LO
Sets the low limit for the first supervised parameter. See
3201
SUPERV 1 PARAM above.
3203 SUPERV 1 LIM HI
Sets the high limit for the first supervised parameter. See
3201
SUPERV 1 PARAM above.
3204 SUPERV 2 PARAM
Selects the second supervised parameter. See 3201
SUPERV 1 PARAM above.
3205 SUPERV 2 LIM LO
Sets the low limit for the second supervised parameter. See 3204
SUPERV 2 PARAM above.
3206 SUPERV 2 LIM HI
Sets the high limit for the second supervised parameter. See 3204
SUPERV 2 PARAM above.
3207 SUPERV 3 PARAM
Selects the third supervised parameter. See 3201
SUPERV 1 PARAM above.
Value of supervised parameter
Case A
0
Energized (1)
0
HI (3203)
t
t
t
LO (3202)
Case B
Energized (1)
LO (3202)
t
HI (3203)
Value of Supervised Parameter
Case A
0
Energized (1)
0
t
t
Case B
Energized (1)
Active Limit

Table of Contents

Other manuals for ABB ACS550-01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS550-01 and is the answer not in the manual?

ABB ACS550-01 Specifications

General IconGeneral
BrandABB
ModelACS550-01
CategoryController
LanguageEnglish

Related product manuals