42 ACS550 User’s Manual
Start-Up
Application Macros
Macros change a group of parameters to new, predefined values. Use macros to
minimize the need for manual editing of parameters. Selecting a macro sets all other
parameters to their default values, except:
• Group 99: Start-up Data parameters (except parameter 9904)
• The PARAMETER LOCK 1602
• The PARAM SAVE 1607
• The COMM FAULT FUNC 3018 and COMM FAULT TIME 3019
• The COMM PROT SEL 9802
• Groups 50…53 parameters
• Group 29 Maintenance triggers
After selecting a macro, additional parameter changes can be made manually using
the control panel.
Application macros are enabled by setting the value for parameter 9902
APPLIC
MACRO. By default, 1, ABB Standard, is the enabled macro.
The following sections describe each of the application macros and provide a
connection example for each macro.
The last section below, "Macro Default Values for Parameters" lists the parameters
that the macros change, and the default values established by each macro.