Table 6-3. CS1 Single Loop CON0 Datapoints
Data-
point Table Module Title and Function
De-
fault
AO0 - Control Out (Cont)
L122 5-9 CON0 Hard Manual Limit - 1 = apply output limits to the final output
of the Auto-Manual Generator. It affects both the manual
push buttons and the controller’s result. 0 = do not apply
limits.
1
C109 5-9 CON0 Output High Limit - Sets maximum Control Output signal
value in engineering units.
100
C110 5-9 CON0 Output Low Limit - Sets minimum Control Output signal value
in engineering units.
0
C118 5-9 CON0 Output Slew Rate - It is a rate limit applied to the output
value. When configured to a non-zero value, the output from
the Auto-Selector is only allowed to change by this amount
each scan time. A zero disables output slewing. It does not
affect manual operation.
0
CON0 Control Related Datapoints
C106 5-9 CON0 Proportional Band - Is the percent of error required to move
the output full scale for proportional action.
100
C107 5-9 CON0 Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.
0
C108 5-9 CON0 Rate Time - Represents the minutes proportional action is
advanced.
0
C111 5-9 CON0 Manual Reset - It determines output valve position when the
controller is in Auto and the error = 0. It is mutually
exclusive with Reset Time.
50
L106 5-9 CON0 Reverse Switch - 0 = Control Output
↑
if PV
↑
; 1 = Control
Output
↓
if PV
↑
.
1
L114 5-9 CON0 Auto Enable - Controller output is from the PID algorithm
when set to 1 and A/M push button is in Auto.
1
C115 5-9 CON0 Controller Span - Enter a value, that when added to the
Controller Lower Range value, will produce the control upper
range value in engineering units.
100
C116 5-9 CON0 Controller Lower Range - Enter a value that represents in
engineering units the control lower range value.
0
AO1 - Retransmitted PV
L473 5-5 AO1 0-20 mA Output - 0 = 4-20 mA signal; 1 = 0-20 mA signal.
Enter a value that matches the required Process Variable
input signal range of the chained controller or device.
0
DI0 - Force Output Tracking
L264 5-6 DI0 Contact Input Invert - Normally, Force Output Tracking is
enabled if DI0 is open (and datapoint L119 - Enable Output
Tracking = 1). Set to 1 to reverse the DI0 condition required
to activated output tracking (DI0 closed = Force Output
Tracking).
0
3 of 5
Section 6. CS1 - Single Loop Controller
6-7