TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
92
Register
Address
Item Scale
Factor
Description
40280 % Fifth Harmonic-B Winding 1 2 Unsigned High Order Byte LSB
40280 % Fifth Harmonic-C Winding 1 2 Unsigned Low Order Byte MSB
40281 % All Harmonic-A Winding 1 2 Unsigned High Order Byte LSB
40281 % All Harmonic-B Winding 1 2 Unsigned Low Order Byte MSB
40282 % All Harmonic-C Winding 1 2 Unsigned High Order Byte LSB
40282 % Second Harmonic-A Winding 2 2 Unsigned Low Order Byte MSB
40283 % Second Harmonic-B Winding 2 2 Unsigned High Order Byte LSB
40283 % Second Harmonic-C Winding 2 2 Unsigned Low Order Byte MSB
40284 % Fifth Harmonic-A Winding 2 2 Unsigned High Order Byte LSB
40284 % Fifth Harmonic-B Winding 2 2 Unsigned Low Order Byte MSB
40285 % Fifth Harmonic-C Winding 2 2 Unsigned High Order Byte LSB
40285 % All Harmonic-A Winding 2 2 Unsigned Low Order Byte MSB
40286 % All Harmonic-B Winding 2 2 Unsigned High Order Byte LSB
40286 % All Harmonic-C Winding 2 2 Unsigned Low Order Byte MSB
40287 % Second Harmonic-A Winding 3 2 Unsigned High Order Byte LSB
40287 % Second Harmonic-B Winding 3 2 Unsigned Low Order Byte MSB
40288 % Second Harmonic-C Winding 3 2 Unsigned High Order Byte LSB
40288 % Fifth Harmonic-A Winding 3 2 Unsigned Low Order Byte MSB
40289 % Fifth Harmonic-B Winding 3 2 Unsigned High Order Byte LSB
40289 % Fifth Harmonic-C Winding 3 2 Unsigned Low Order Byte MSB
40290 % All Harmonic-A Winding 3 2 Unsigned High Order Byte LSB
40290 % All Harmonic-B Winding 3 2 Unsigned Low Order Byte MSB
40291 % All Harmonic-C Winding 3 2 Unsigned High Order Byte LSB
40291 Current Tap Scale Winding 1 10 Unsigned Low Order Byte MSB
40292 Current Tap Scale Winding 2 10 Unsigned High Order Byte LSB
40292 Current Tap Scale Winding 3 10 Unsigned Low Order Byte MSB
Load Current and Angular Values (63 Registers Defined TPU 2 Winding – 66 Registers
Defined TPU 3 Winding)
Load Currents for the windings are reported in Registers 40385 though 40447 for a Two Winding
TPU2000/2000R. If the Modbus card is inserted in a 3 Winding Unit, the status is reported in 40385 through
40450. Ground Current Angles and Magnitudes were added in version X.XX flash executives and version 1.80
Modbus chipsets.
Table 5-20. Demand Metering Modbus Address Map Definition
Register
Address
Item Description
40385 Load Current A Winding 1 Unsigned 32 Bit High Order Word MSW
40386 Load Current A Winding 1 Unsigned 32 Bit Low Order Word LSW
40387 Load Current B Winding 1 Unsigned 32 Bit High Order Word MSW
40388 Load Current B Winding 1 Unsigned 32 Bit Low Order Word LSW
40389 Load Current C Winding 1 Unsigned 32 Bit High Order Word MSW
40390 Load Current C Winding 1 Unsigned 32 Bit Low Order Word LSW
40391 Load Current N Winding 1 Unsigned 32 Bit High Order Word MSW
40392 Load Current N Winding 1 Unsigned 32 Bit Low Order Word LSW
40393 Load Current A Winding 2 Unsigned 32 Bit High Order Word MSW
40394 Load Current A Winding 2 Unsigned 32 Bit Low Order Word LSW
40395 Load Current B Winding 2 Unsigned 32 Bit High Order Word MSW
40396 Load Current B Winding 2 Unsigned 32 Bit Low Order Word LSW
40397 Load Current C Winding 2 Unsigned 32 Bit High Order Word MSW
40398 Load Current C Winding 2 Unsigned 32 Bit Low Order Word LSW