TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
160
Table 5-54. Oscillographic Configuration Registers
Register Item Description
63968 Execute Register Unsigned Integer 16 Bits
0 = No Action
1 = Transfer Settings
2 = Retrieve Settings
63969 Access Password 2 Leftmost Digits ASCII
63970 Access Password 2 Rightmost Digits ASCII
63971 Reserved Reserved
63972 Start/Stop Accumulation Unsigned Integer 16 Bits
0 = Stop
1 = Start
63973 Acquisition Format Unsigned Integer 16 Bits
0 = 8 Records Max Storage/8 Cycles/Record
1 = 4 Records Max Storage/16 Cycles/Record
2 = 2 Records Max Storage/32 Cycles/Record
3 = 1 Record Stored/64 Cycles/Record
63974 Trigger Mode Unsigned Integer 16 Bits
0 = Normal
1 = Single Shot
2 = Normal/Append Mode
3 = Single Shot/Append Mode
63975 Trigger Position Unsigned Integer 16 Bits
Number of quarter cycles to capture pre-fault.
If 63077 = 0 : 0 <= Trigger <= 32
If 63077 = 1 : 0 <= Trigger <= 64
If 63077 = 2 : 0 <= Trigger <= 128
If 63077 = 3 : 0 <= Trigger <= 256
63976 Trigger Flag
Reserved
Unsigned Integer 16 Bits
Set to zero
63977 Trigger Flag
Reserved
Unsigned Integer 16 Bits
Set to 0
63978 Trigger Flag
Bit 0 = Master Trip (lsb)
Bit 1 = Breaker Open
Bit 2 = WCI
Bit 3 = Reserved
Bit 4 = Reserved
Bit 5 = Reserved
Bit 6 = Reserved
Bit 7 = Reserved
Bit 8 = Reserved
Bit 9 = Reserved
Bit 10 = Reserved
Bit 11 = Reserved
Bit 12 = Reserved
Bit 13 = Reserved
Bit 14 = Reserved
Bit 15 = Reserved
Unsigned Integer 16 Bits
Start Capture on Master Trip State
Start Capture on Breaker Open
Start Capture on Waveform Capture Initiate
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
63979 Trigger Flag
Bit 0 = 87T (lsb)
Bit 1 = 87H
Bit 2 = 51P-1
Bit 3 = 51N-1
Bit 4 = 50P-1
Bit 5 = 50N-1
Unsigned Integer 16 Bits Start Capture on:
3 Phase % Differential Current Control
3 Phase Instantaneous Differential Current Control
Winding 1 Phase Time Overcurrent Control
Winding 1 Neutral Time Overcurrent Control
Winding 1 Phase Instantaneous Overcurrent Control
1
st
Winding 1 Neutral Instantaneous Overcurrent Control