TPU2000/2000R Modbus/Modbus Plus Automation Guide
207
Register
Address
Item Description
63483 51G-3 Curve Select (TYPE II) Unsigned 16 Bits
Range 0-12 (See Text Above)
63484 51G-3 Pickup Amps Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
63485 51G-3 Time Dial/Time Delay Unsigned 16 Bits
1<=Range <=10 * 20 : Time Dial
0<=Range<=10 * 20 : Time Delay
63486 50G-3 Curve Select Byte (TYPE II) Unsigned Integer 16 bits
0<=Range<=12 (See Text Above)
63487 51G-3 Pickup Amps Unsigned 16 Bits
0.5<=Range<= 20 *10
63488 51G-3 Time Dial/Delay Setting Unsigned 16 Bits
Time Dial * 10
Delay * 100
63489 150G-3 Curve Select (TYPE II) Unsigned Integer 16 bits
See Table Above
63490 150G-3 Pickup Amps Unsigned 16 Bits
0.5<=Range<= 20 *10
63491 150G-3 Time Delay Unsigned 16 Bits
0<=Range<=9.99 * 100
63492 Disturb 3 Pickup X Unsigned Integer 16 Bits
0.5<= Range<=5 *10
63493 Level Detector-1 Pickup X Unsigned Integer 16 Bits
0.5<= Range<=20 *10 , 201 = Disable
Configuration Settings
The TPU2000 and TPU2000R has configuration settings which may be set through the unit’s Front Panel
Interface (FPI), ECP (External Communication Program), WinECP (WINdows External Communication Program)
or via Modbus/Modbus Plus via Registers 61458 through 61445. Table 5-72 is for the TPU2000 2 Winding units
and the TPU2000R 2 and 3 Winding Units.
Table 5-72. TPU2000/2000R Configuration Setting Register Setting
Register
Address
Item Description
61408 SPARE_1
61409 Execute Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
Unsigned 16 Bit
61410 Access Password ASCII – 2 Characters Leftmost Digits
61411 Access Password ASCII – 2 Characters Rightmost Digits
61412 SPARE_2
61413 Winding 1 Phase CT Ratio Unsigned Integer 16 Bits
1<=Range<=4000
61414 Winding 1 Neutral CT Ratio Unsigned Integer 16 Bits
1<=Range<=4000
61415 Winding 2 Phase CT Ratio Unsigned Integer 16 Bits
1<=Range<=4000
61416 Winding 2 Neutral CT Ratio Unsigned Integer 16 Bits
1<=Range<=4000
61417 Winding Phase Comp Unsigned Integer 16 Bits