211
61674 Phase Demand Unsigned Integer
0<=Range <=9999
61675 Neutral Demand Unsigned Integer
0<=Range <=9999
61676 Load Current Alarms Unsigned Integer 16 Bits
0<=Range <=9999
61677 3 Phase Demand Alarm Unsigned Integer 16 Bits
10<=Range <=9999 , 10000 Disables
61678 Low PF Alarm Unsigned Integer 16 Bits
0.5<=Range <=1.0 *100 , 101 Disables
61679 High PF Alarm Unsigned Integer 16 Bits
0.5<=Range <=1.0 *100 , 101 Disables
61680 Positive KVAR Alarm Unsigned Integer 16 Bits
10<=Range <=99990/10 , 10000 Disables
61681 Negative KVAR Alarm Unsigned Integer 16 Bits
10<=Range <=99990/10 , 10000 Disables
61682 Positive Watt Alarm 1 Unsigned Integer 16 Bits
0<=Range <=9999 , 10000 Disables
62683 Positive Watt Alarm 2 Unsigned Integer 16 Bits
0<=Range <=9999 , 10000 Disables
Table 5-76. 3 Winding Alarm Settings Block
Register
Address
Item Description
63840 SPARE_1
63841 Execute Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
Unsigned 16 Bits
63842 Access Password ASCII – 2 Characters Leftmost Digits
63843 Access Password ASCII – 2 Characters Rightmost Digits
63844 SPARE_2
63845 Positive Watt Alarm 2 Unsigned Integer 16 Bits
0<=Range <=9999 , 10000 Disables
63846 Through Fault Summation KSI
Alarm – Winding 3.
Unsigned Integer 16 Bits
0<=Range <=9999
Real Time Clock (13 Registers Defined)
The real time clock data can be set via the network. This clock is the master which is used to time stamp
operational records and event records in Registers 41029 through 41036 (as defined in Table 17) and Registers
41284 through 41291 (as defined in Table 20). It should be noted that the clock registers have been updated to
reflect the four digit year required for Y2K compliance in time reporting.
If the month is set to 0, the real time clock is disabled. The real time clock cannot be enabled or disabled via
Modbus. The real time clock may only be disabled via TPU2000/TPU2000R Standard 10 Byte Protocol
Attached hereto and referenced in Appendix A.
Table 5-77 lists the register definition for Real Time Clock configuration.
Table 5-77. Real Time Clock Register Definition Assignment
Register
Address
Item Description
61792 SPARE_1
61793 Execute Register
0 = No Action
Unsigned 16 Bits