TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
58
Register
Address
Item Description
3 00838: PWatt3 Winding 3 Positive 3 Phase kWatt Alarm Energized
3 00839: OCA Gnd Ground Overcurrent Alarm Energized
3 00840: OCA Gnd Ground Overcurrent Alarm Energized
Physical Output Block (Single Bit Data) – 16 Discrete Coils (8 Elements Defined)
Output status is described in Table 5-2. The state of the addresses 00257 through 00272 follow the state of the
physical output hardware contacts located at the rear screw terminals of the relay. It should be noted that some
of the Physical Output contact status information is not available in the TPU2000R. Table 5-2 notes the elements,
which are undefined in the TPU2000R. The TPU2000R has six physical output contacts, which are map-able via
ECP software. The TPU2000R has a single dedicated physical output contact defined as TRIP. The TPU2000
has seven map-able physical output contacts (1 through 7) and a dedicated TRIP contact. The status of the
element mirrors that of the physical contact and that reported through the TPU2000/2000R front panel interface of
through the ECP or WinECP configuration program.
Table 5-2. Physical Output Contact Mapping Defined
Discrete Address Item Description
00257: Spare Reserved
00258: Spare Reserved
00259: Spare Reserved
00260: Spare Reserved
00261: Spare Reserved
00262: Spare Reserved
00263: Spare Reserved
00264: Spare Reserved
00265: OUT7 Physical Output Contact 7
00266: OUT 6 Physical Output Contact 6
00267: OUT5 Physical Output Contact 5
00268: OUT4 Physical Output Contact 4
00269: OUT3 Physical Output Contact 3
00270: OUT2 Physical Output Contact 2
00271: OUT1 Physical Output Contact 1
00272: TRIP Breaker Trip Physical Output Contact
Logical Output Block (Two Bit Data with Momentary Change Detection)
Modbus does not support features commonly required within the utility industry. However, the protocol may easily
be adapted to support features required. It is most important that no event is to be missed by a polling host when
a device is not accessed. To this end, a feature has been developed which ensures that the status of the data
change is always reported. Table 5-3 lists the Momentary Logical Output Mapping.
Table 5-3. Momentary Change Detect Data Definition
Register
Address
Item Description
00001 DIFF Differential Trip Contact Energized
00002 SELFCHECK
ALARM
Self Check Alarm Energized
00003 87T Harmonic Restrained % Differential Trip Alarm Energized
00004 87H Unrestrained High Set Instantaneous Differential Trip Alarm Energized
00005 2HROA 2
nd
Harmonic Restraint Alarm Energized
00006 5HROA 5
th
Harmonic Restraint Alarm Energized
00007 AHROA All Harmonics Restraint Alarm (2
nd
through 11th Harmonic) Energized
00008 TCFA Trip Circuit is Open Fail Alarm Energized