TPU2000/2000R Modbus/Modbus Plus Automation Guide
179
Function 20 Read Gen.Ref.
Modbus Host
Slave
Addr.
Funct.
Code
14
Error
Check
Read
Addr
HI
Read
Addr
LO
#Regs
Read
HI
#Regs
Read
LO
Byte
Count
*
Ref
Type
06
File
Num
HI
File
Num
LO
Sub Request 01
Sub Request XX
E
C
Modbus Slave Addr =1
SOT
Slave
Addr.
Funct.
Code
14
Data
LO
Data
HI
Byte 1 …2……..3…….4…….5……6……..7…. 8……...………………………………………..…..X
Data
HI
Data
LO
Error
Check
Byte
Count
*
Req1
Byte
Count
%
Ref
Type
06
Sub Response 01 Sub Response 02
SOT
EOT
Total length of response
not be be > 256 Bytes.
Req2
Byte
Count
%
MSB
LSB
151413121110 9 8 76543210
MSB
LSB
Figure 5-64. Function 20 Read 6x Register Frame Definition
Function 21 Read Gen.Ref.
Modbus Host
Slave
Addr.
Funct.
Code
15
Error
Check
Read
Addr
HI
Read
Addr
LO
#Regs
Read
HI
#Regs
Read
LO
Byte
Count
*
Ref
Type
06
File
Num
HI
File
Num
LO
Sub Request 01
Sub Request XX
E
C
Modbus Slave Addr =1
SOT
Slave
Addr.
Funct.
Code
15
Data
LO
Data
HI
Byte 1 …2……..3…….4…….5……6……..7…. 8……...………………………………………..…..X
Data
HI
Data
LO
Error
Check
Byte
Count
*
Req1
Byte
Count
%
Ref
Type
06
Sub Response 01 Sub Response 02
SOT
EOT
Total length of response
not be be > 256 Bytes.
Req2
Byte
Count
%
MSB
LSB
151413121110 9 8 76543210
MSB
LSB
Figure 5-65. Modbus Command 21 - Write General Reference Format
IMPLEMENTATION TIP- When 6x Registers Are Written, A 10 Minute Execute Timer Is Initiated Upon The First
Write To A 6x Block. If The Execute Register Is Not Written With A Value Of 1 Within The 10 Minutes Of The
Initial Write, The 6x Veiwable Register Segment Will Be Restored To The Original Values From The
“TPU2000/TPU2000R’s” Internal Flash Ram Memory.
Programmable Input Configuration
The TPU2000/TPU2000R allows for query or changing of Relay Configuration Data via the Modbus ASCII
protocol. Table 23 further describes the register assignment for viewing or changing the TPU2000/TPU2000R
parameters.
Term Definitions
The parameterization may be configured via ECP or WinECP. However changing the Programmable Input
Configuration is slightly more involved through Modbus Plus or Modbus. A few terms must be understood before
discussing the procedure for changing the 6X memory Programmable Input parameters.