TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
112
Bit 9 = FLI 7
Bit 8 = FLI 8
Bit 7 = FLI 9
Bit 6 = FLI 10
Bit 5 = FLI 11
Bit 4 = FLI 12
Bit 3 = FLI 13
Bit 2 = FLI 14
Bit 1 = FLI 15
Bit 0 = FLI 16
0 = Normal, 1 = Forced
0 = Normal, 1 = Forced
0 = Normal, 1 = Forced
0 = Normal, 1 = Forced
0 = Normal, 1 = Forced
0 = Normal, 1 = Forced
0 = Normal, 1 = Forced
0 = Normal, 1 = Forced
0 = Normal, 1 = Forced
0 = Normal, 1 = Forced (lsb rightmost bit)
41177 FORCED LOGICAL IN
Bit 15 = FLI 17
Bit 14 = FLI 18
Bit 13 = FLI 19
Bit 12 = FLI 20
Bit 11 = FLI 21
Bit 10 = FLI 22
Bit 9 = FLI 23
Bit 8 = FLI 24
Bit 7 = FLI 25
Bit 6 = FLI 26
Bit 5 = FLI 27
Bit 4 = FLI 28
Bit 3 = FLI 29
Bit 2 = FLI 30
Bit 1 = FLI 31
Bit 0 = FLI 32
Unsigned Integer 16 Bits FLI Point State
0 = De-energized, 1 = Energized (msb leftmost bit)
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized (lsb rightmost bit)
41178 FORCED LOGICAL IN
Bit 15 = FLI 1
Bit 14 = FLI 2
Bit 13 = FLI 3
Bit 12 = FLI 4
Bit 11 = FLI 5
Bit 10 = FLI 6
Bit 9 = FLI 7
Bit 8 = FLI 8
Bit 7 = FLI 9
Bit 6 = FLI 10
Bit 5 = FLI 11
Bit 4 = FLI 12
Bit 3 = FLI 13
Bit 2 = FLI 14
Bit 1 = FLI 15
Bit 0 = FLI 16
Unsigned Integer 16 Bits
0 = De-energized, 1 = Energized (msb leftmost bit)
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized
0 = De-energized, 1 = Energized (lsb rightmost bit)
Table 5-31. Three Winding Logical Output Points
Register
Address
Item Description
41179 Phys Out
Bit 15 = 51P-3
Bit 14 =50P-3
Bit 13 = 150P-3
Bit 12 = 51N-3
Bit 11 = 50N-3
Bit 10 = 150N-3
Bit 9 = 46-3
Bit 8 = 51G
16 Bit Unsigned Integer Physical Output Select Status
Winding 3 Phase Time Overcurrent Alarm (msb leftmost bit)
1
st
Winding 3 Phase Instantaneous Overcurrent Alarm
2
nd
Winding 3 Phase Instantaneous Overcurrent Alarm
Winding 3 Neutral Time Overcurrent Alarm
1
st
Winding 3 Neutral Instantaneous Overcurrent Alarm
2
nd
Winding 3 Neutral Instantaneous Overcurrent Alarm
Winding 3 Negative Sequence Time Overcurrent Alarm
1
st
Ground Instantaneous Overcurrent Alarm

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB TPU2000 and is the answer not in the manual?

ABB TPU2000 Specifications

General IconGeneral
BrandABB
ModelTPU2000
CategoryComputer Hardware
LanguageEnglish

Related product manuals