EasyManuals Logo
Home>ABB>Computer Hardware>TPU2000

ABB TPU2000 User Manual

ABB TPU2000
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #171 background imageLoading...
Page #171 background image
TPU2000/2000R Modbus/Modbus Plus Automation Guide
161
Register Item Description
Bit 6 = 150P-1
Bit 7 = 150N-1
Bit 8 = 46-1
Bit 9 = 51P-2
Bit10 = 51G (3 Winding)
51G-2 (2 Winding)
Bit 11 = 50P-2
Bit 12 = 50G (3 Winding)
50G-2 (2 Winding)
Bit 13 = 150P-2
Bit 14 = 150G (3 Winding)
150N-2 (2 Winding)
Bit 15 = 46-2 (msb)
2
nd
Winding 1 Phase Instantaneous Overcurrent Control
2
nd
Winding 1 Neutral Instantaneous Overcurrent Control
Winding 1 Negative Sequence Control
Winding 2 Phase Instantaneous Overcurrent Control
Ground Time Overcurrent Control
Winding 2 Ground Time Overcurrent Control
Winding 2 Phase Instantaneous Overcurrent Control
1
st
Ground Time Overcurrent Control
1
st
Winding 2 Ground Time Overcurrent Control
2
nd
Winding 2 Phase Time Overcurrent Control
2
nd
Ground Instantaneous Control
2
nd
Winding 2 Neutral Phase Instantaneous Control
Winding 2 Negative Sequence Control
63980 Bit 0 = Thru Fault (lsb)
Bit 1 = Harmonic Restraint
Bit 2 = External Input
Bit 3 = 51P-3 (3 Winding Only)
Bit 4 = 51N-3 (3 Winding Only)
Bit 5 = 50P-3 (3 Winding Only)
Bit 6 = 50N-3 (3 Winding Only)
Bit 7 = 150P-3 (3 Winding Only)
Bit 8 = 150N-3 (3 Winding Only)
Bit 9 = 46-3 (3 Winding Only)
Bit 10 = 51N-2 (3 Winding Only)
Bit 11 = 50N-2 (3 Winding Only)
Bit 12 = 150N-2 (3 Winding
Only)
Bit 13 = Reserved
Bit 14 = Reserved
Bit 15 = Reserved (msb)
Through Fault Control
Harmonic Restraint Control
External Input Control
Winding 3 Phase Time Overcurrent Control
Winding 3 Neutral Time Overcurrent Control
1
st
Winding 3 Phase Instantaneous Overcurrent Control
1
st
Winding 3 Neutral Inst. Overcurrent Control
2
nd
Winding 3 Phase Instantaneous Overcurrent Control
2
nd
Winding 3 Neutral Instantaneous Overcurrent Control
Winding 3 Negative Sequence Control
Winding 3 Neutral Time Overcurrent Control
1
st
Winding 3 Neutral Inst. Overcurrent Control
2
nd
Winding 3 Neutral Inst. Overcurrent Control
63084 Reserved Reserved
63085-
63199
Reserved Reserved
OSCILLOGRAPHICS 6X DATA RETRIEVAL MAP
TPU REGISTER MAP MEMORY
Data Control Register
Oscillographic
Configuration
Settings
63968
63969
63199
E
C
INTERNAL
TPU MEMORY
Non-Volatile
Send Value “2” to
Control Register 63968
Send Password to Registers
63969 and 63970
Not Viewable
By Operator
Viewable
Via Modbus/Modbus Plus
OSCILLOGRAPHICS 6X STORAGE MAP
TPU REGISTER MAP MEMORY
Data Control Register
Oscillographic
Configuration
Settings
63968
63969
63199
..
E
C
INTERNAL
TPU MEMORY
Non-Volatile
Send “Data” to
Registers 63972 -63199
(Oscillographic Configuration)
Not Viewable
By Operator
Viewable
Via Modbus/Modbus Plus
Reset to 0.
Send a Value of 1 to Relay to
Save Configuration Data. Send Password to
Registers 63969 and 63970
Write a 0
to Control
Register
Figure 5-60. Oscillographics Retrieval/Storage Parameterization Philosophy

Table of Contents