216 Rockwell Automation Publication 750-IN001P-EN-P - April 2017
Chapter 4 Power Wiring
Wall Mount Frames 1…7
Table 43 - Power Jumper Default Configurations
Floor Mount Frames 8…10
Table 44 - Power Jumper Default Configurations
Table 45 - Recommended Power Jumper Configurations Wall Mount Frames 1…7
IMPORTANT PowerFlex 750-Series drives, Frames 1…7, leave the factory with jumpers
PE-A and PE-B in one of two possible configurations. Reconfigure these
jumpers based on the power source type available.
Cat. No. Position 11 Jumper PE-A
(MOV/Input filter caps)
Jumper PE-B
(DC bus common mode caps)
A Connected Disconnected
J Connected Connected
IMPORTANT PowerFlex 750-Series drives, Frames 8…10, leave the factory with jumpers
PE-A1, PE-A2, and PE-B in one of two possible configurations. Reconfigure
these jumpers based on the power source type available.
Cat. No. Position 11 Jumper PE-A1
(MOV)
Jumper PE-A2
(input filter caps)
Jumper PE-B
(DC bus common mode caps)
A Connected Connected Disconnected
J Connected Connected Connected
ATTENTION: Risk of equipment damage exists. The drive power source type
must be accurately determined. Jumpers PE-A, PE-A1, PE-A2, and PE-B must
be configured for the power source type according to the recommendations
in Table 45
.
Power Source Type Jumper PE-A
(1)
(2)
(MOV/input filter
caps)
(1) When MOVs are disconnected, the power system must have its own transient protection to confirm known and controlled
voltages.
(2) Frame 5…7 common DC input drives do not have the PE-A jumper.
Jumper PE-B
(DC bus common
mode caps)
Benefits Of Correct
Configuration on Power Source
Type
Non-Solid Ground
AC fed ungrounded
Impedance grounded
•B phase ground
DC fed from an active
converter
Disconnected Disconnected Helps avoid severe equipment
damage when ground fault occurs
Solid Ground
AC fed solidly grounded
DC fed from passive
rectifier that has a solidly
grounded AC source
Connected Connected UL compliance
Reduced electrical noise
Most stable operation
EMC compliance
Reduced voltage stress on
components and motor bearings

Table of Contents

Other manuals for Allen-Bradley 20F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 20F and is the answer not in the manual?

Allen-Bradley 20F Specifications

General IconGeneral
BrandAllen-Bradley
Model20F
CategoryController
LanguageEnglish

Related product manuals