Publication 1766-RM001A-EN-P - October 2008
Relay-Type (Bit) Instructions 169
OTE - Output Energize
Instruction Type: output
Use an OTE instruction to turn a bit location on when rung conditions are
evaluated as true and off when the rung is evaluated as false. An example
of a device that turns on or off is an output wired to a pilot light
(addressed as O0:0/4). OTE instructions are reset (turned OFF) when:
• You enter or return to the program or remote program mode or
power is restored.
• The OTE is programmed within an inactive or false Master Control
Reset (MCR) zone.
B3:0
1
Execution Time for the OTE Instructions
Controller When Rung Is:
True False
MicroLogix 1400 0.2685 µs 0.2629 µs
TIP
A bit that is set within a subroutine using an OTE instruction remains set
until the OTE is scanned again.
ATTENTION
If you enable interrupts during the program scan via an OTL, OTE, or UIE,
this instruction must be the last instruction executed on the rung (last
instruction on last branch). It is recommended this be the only output
instruction on the rung.
ATTENTION
Never use an output address at more than one place in your logic program.
Always be fully aware of the load represented by the output coil.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1400 and is the answer not in the manual?

Allen-Bradley MicroLogix 1400 Specifications

General IconGeneral
BrandAllen-Bradley
ModelMicroLogix 1400
CategoryController
LanguageEnglish

Related product manuals