178 Rockwell Automation Publication 7000-UM202D-EN-P - May 2018
Appendix A Specifications
Communication Protocols
(Optional)
DeviceNet ControlNet
Ethernet I/P Lon Works
Dual-port Ethernet I/P Can Open
Profibus RS485 HVAC
Modbus RS485 DF1
Interbus RS232 DF1
USB
Enclosure Type 1 IP21 (with door gaskets)
IP42 (optional)
Lifting Device Standard / Removable
Mounting Arrangement Mounting Sill Channels
Structure Finish Epoxy Powder – Paint
Exterior Sandtex Light Grey (RAL 7038) – Black (RAL 8022)
Internal – Control Sub Plates – High Gloss White (RAL 9003)
Interlocking Key provision for customer input Disconnecting Device
Corrosion Protection Unpainted Parts (Zn chromate)
Ambient Temperature 0…40 °C (32…104 °F) / 0…50 °C (32…122 °F) - optional
Fiber Optic Interface Rectifier – Inverter – Cabinet (Warning / Trip)
Door Filter Painted Defuser with Matted Filter Media
Door Filter Blockage Air Flow Restriction Trip / Warning
Storage and Transportation
Temperature Range
-40…+70 °C (-40…+185 °F)
Relative Humidity Max. 95%, non-condensing
Altitude (Standard) 0…1000 m (0…3300 ft)
Altitude (Optional) 1001…5000 m (3300…16,400 ft)
Seismic (UBC Rating) 1, 2, 3, 4
Standards NEMA, IEC, CSA, UL, ANSI, IEEE
(1) Voltage Sag tolerance is reduced to -25% when control power is supplied from medium voltage via CPT.
(2) MOVs are used for 18-pulse. Surge arrestors are used for AFE/Direct-to-Drive configurations.
(3) Short-circuit fault rating based on input protection device (contactor or circuit breaker).
(4) BIL rating based on altitudes < 1000 m (3300 ft) Refer to factory for derating on altitudes >1000 m.
(5) Optional.
(6) Under certain conditions, power system analysis will be required.
Table 17 - General Design Specifications (Continued)
Description