Operation Mode
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 18
3.8 Resounding the Internal Buzzer
When pressing the Mute Panel button in an alarm condition, the
internal buzzer will automatically be resounded in the following cases:
 if any new event occurs (for example, a detection zone enters the
Fire Alarm state)
 after a timeout period, if the cause for making it sound is still
present
3.9 Resounding Fire Alarm Devices
When pressing the Silence button in the event of an alarm, all Fire
Alarm Devices (FADs) will be deactivated. The red Fire Alarm
indication lamp will switch from a pulsing to a steady light and the
local buzzer will go off.
At this stage, the resound timer will start (if it has been configured).
The resound timer will restart on each operation of the Silence button.
Holding the Silence button down for more than 5 seconds will activate
the Resound function.
The alarm zones are automatically resounded to their alarm states on
timeout (configurable) of the Silence resound timer.
3.10 Disablement Sources
3.10.1 Overview
Autroprime supports the following disablement sources:
 Individual
A unit is disabled by an individual command issued to the specified
unit. Applicable to all units with disabling capabilities.
 Loop
A unit is disabled by its corresponding loop being disabled.
Applicable to points, FADs, FPEs and panels connected to loops
(DID).
 Detection Zone
A point is disabled by a command to its corresponding detection
zone, affecting all points in the detection zone, including any
manual call points. Applicable to points only.
 Alarm Zone
FADs in an alarm zone will be disabled.
 Disable Input Unit
A detection zone is disabled by a command from a Disable Input
Unit. Applicable to detection zones only.
 Modbus

Table of Contents

Other manuals for Autronica Autroprime

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autroprime and is the answer not in the manual?

Autronica Autroprime Specifications

General IconGeneral
BrandAutronica
ModelAutroprime
CategoryFire Alarms
LanguageEnglish

Related product manuals