Service Commands
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 70
16.4 Testing Alarm Zones
This manual test activates all Fire Alarm Devices (FADs) in a selected
alarm zone (with audible indication).
The duration of the signal and the interval between each signal are
configurable (normally 1 second ON and 30 seconds OFF). The test
signal is given the lowest priority. In the event of an alarm, the alarm
signal will thus override the test signal.
From the Service Menu, perform the following:
 Use the arrow down button to scroll downwards to
Unit Test, then press Enter.
 Scroll down to Alarm Zone.
 Press Enter once more.
 Use the arrow button to select the Alarm Zone that
is to be tested. Use, if necessary, the multiselect feature to select
several alarm zones.
 Press the Function button
 To start the test, press Enter.
 Press Enter once more to confirm.
 To stop the test, use the arrow button to select Stop Test, then
press Enter twice.
16.5 Testing Fire Alarm Devices
This chapter describes how to test each Fire Alarm Device (FAD)
individually.
When the test is initiated for a selected Fire Alarm Device (FAD), a
test signal will be sent to the FAD.
The duration of the signal and the interval between each signal are
configurable (normally 1 s econd ON and 30 seconds OFF). The test
signal is given the lowest priority. In the event of an alarm, the alarm
signal will thus override the test signal.
From the Service Menu, perform the following:
 Use the arrow down button to scroll downwards to
Unit Test, then press Enter.
 Press Enter once more.
 Use the arrow button to select the Fire Alarm Device (FAD) that
is to be tested. Use, if necessary, the multiselect feature to select
several Fire Alarm Devices.
 Press the Function button
 To start the test, press Enter.
 Press Enter once more to confirm.
 To stop the test, use the arrow button to select Stop Test, then
press Enter twice.

Table of Contents

Other manuals for Autronica Autroprime

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autroprime and is the answer not in the manual?

Autronica Autroprime Specifications

General IconGeneral
BrandAutronica
ModelAutroprime
CategoryFire Alarms
LanguageEnglish

Related product manuals