In the Event of a Fire Alarm -
with Alarm Delay
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 34
7. In the Event of a Fire Alarm -
with Alarm Delay
7.1 Indications - Fire Alarm with Alarm Delay
|
The red Alarm indicator is pulsing.
The total number of detection zones
in alarm state.
The text display presents the
detection zone(s) in alarm state and
their location. By operating the
menu, detailed information is
available.
The remaining time of the delay
period (countdown T1).
The red More Events indicator is
pulsing if several detection zones
are signaling a Fire Alarm with
delay.
The Delayed Activation indicator
has a steady yellow light.
The internal buzzer is activated.
7.2 Actions to be Taken - Fire Alarm with Alarm Delay
Step Actions to be taken Display Indication Audible Indication
1
Follow all precautions
described in the local
fire instructions, step by
step.
The internal buzzer on
the operator panel is
turned on. No fire
alarm devices are
activated (sounders
and visual indicators).
Comments: The first detection zone and point(s) in alarm (and last detection zone, if
several) are highlighted in the display. The total number of detection zones in
alarm state is shown in the upper right corner of the display. The delay period
T1 is counted down, the remaining time is shown on the bottom line.
The red Alarm indicator is pulsing. If an output to Fire Alarm Routing
Equipment is configured and applied, the red Remote Call indicator will also
be pulsing.
When several zones are in alarm state, the More Events indicator is pulsing.
A point is sending an alarm signal from a Delayed Action detection zone and the system is set to
Day Mode (alarm delay is active). NOTE: An alarm from a manual call point is normally configured
to give immediate actioning on the alarm outputs even though the system is set to Day Mode
provided that the point has been set to Override Delay and Dependency (YES).
Only the operating buttons that are available and