EasyManuals Logo
Home>Autronica>Fire Alarms>BS-310

Autronica BS-310 User Manual

Autronica BS-310
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 102
14.4.1 Events
To be able to analyse system behaviour for service and maintenance
purposes, a number of events are recorded.
The table below gives an overview of these events and the detailed
information that can be shown on the panel’s display, or on a printout.
Event Detailed Information
Fire Alarms
Date, time and identity of detection zones entering the Fire Alarm state.
Prealarms
Date, time and identity of detection zones entering the Prealarm state.
Early Warnings
Date, time and identity of detection zones entering the Early Warning
state.
Faults
Date, time and identity of subject (individual component, group, zone)
issuing a fault warning signal.
Enable/Disable
Date, time and identity of subject (individual component, group, zone)
entering the disabled state.
Date, time and identity of subject (individual component, group, zone)
exiting the disabled state.
User Operations
The date, time and operation zone identity of the operation of push
buttons; RESET and SILENCE ALARMS.
The date, time and operation zone identity of the operation of;
ALARM_DISABLE, REACTIVATE, RESOUND, INIT, ACTIVATE_ALARM,
ENABLE IMM_ACT, DISABLE_IMM ACT, SET_TIME.
The date, time and event id (detection zone identity, fault identity etc) of all
operations of ACCEPT.
Tests
Date, time and identity of all manually initiated tests.
All Events
All events
Log Setup
Read parameters, read filter, clear log.
www.ukpanels.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica BS-310 and is the answer not in the manual?

Autronica BS-310 Specifications

General IconGeneral
BrandAutronica
ModelBS-310
CategoryFire Alarms
LanguageEnglish

Related product manuals