Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 102
14.4.1 Events
To be able to analyse system behaviour for service and maintenance
purposes, a number of events are recorded.
The table below gives an overview of these events and the detailed
information that can be shown on the panel’s display, or on a printout.
Event Detailed Information
Fire Alarms
•
Date, time and identity of detection zones entering the Fire Alarm state.
Prealarms
•
Date, time and identity of detection zones entering the Prealarm state.
Early Warnings
•
Date, time and identity of detection zones entering the Early Warning
state.
Faults
•
Date, time and identity of subject (individual component, group, zone)
issuing a fault warning signal.
Enable/Disable
•
Date, time and identity of subject (individual component, group, zone)
entering the disabled state.
•
Date, time and identity of subject (individual component, group, zone)
exiting the disabled state.
User Operations
•
The date, time and operation zone identity of the operation of push
buttons; RESET and SILENCE ALARMS.
•
The date, time and operation zone identity of the operation of;
ALARM_DISABLE, REACTIVATE, RESOUND, INIT, ACTIVATE_ALARM,
ENABLE IMM_ACT, DISABLE_IMM ACT, SET_TIME.
•
The date, time and event id (detection zone identity, fault identity etc) of all
operations of ACCEPT.
Tests
•
Date, time and identity of all manually initiated tests.
All Events
•
All events
Log Setup
•
Read parameters, read filter, clear log.