EasyManuals Logo
Home>Autronica>Fire Alarms>BS-310

Autronica BS-310 User Manual

Autronica BS-310
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 115
14.6 Oil & Gas Inhibit
All loop input units can be inhibited. When one or several points are
inhibited, the point(s) will not signal alarm to outputs. An inhibited point
will however present an alarm, prealarm and early warning on all
panels and AutroCom as usual. This includes panel buzzer, panel
LEDs and panel LCD display. The function is specifically related to the
Oil & Gas Market.
It is only possible to inhibit a unit from the panel menu or via
AutroCom. An inhibited point will be inhibited until the unit is un-
inhibited, i.e. no timeout.
Inhibit Point
Cancel Inhibit Point
Oil & Gas Inhibit
Figure 14-5: Loop Commands Menu
14.6.1 Inhibit Point
The procedure describes how to inhibit point(s).
Step Actions to be taken Display Indication
1
To enter the Main Menu, press
!
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SERVICE, press 5.
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT
www.ukpanels.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica BS-310 and is the answer not in the manual?

Autronica BS-310 Specifications

General IconGeneral
BrandAutronica
ModelBS-310
CategoryFire Alarms
LanguageEnglish

Related product manuals