14.5 Loop Commands
Clear Topology
Disable Loop
Enable Loop
Loop Commands
Figure 14-4: Loop Commands Menu
14.5.1 Clear Topology
In situations where the loop topology has been changed in some way,
for example, two detectors have changed places or have been
removed, the service command Clear Topology has to be executed.
Note that when this command is completed, the control panel has to
be initialized manually (see chapter 13.8).
Step Actions to be taken Display Indication
1
To enter the Main Menu, press
!
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SERVICE, press 5.
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT