Auxiliary Boards
Two AUX boards, AUX Board A (address 84) and AUX Board
B (address 85), are installed in each unit. Each of the AUX
boards has a set of jumpers, JP1 and JP2, which must be placed
on the "P" terminal and as shown in Fig. 20. The AUX boards
respond to commands from the Carrier Controller module and
send the Carrier Controller module the results of the channels
they monitor via the LEN. See Table 9 for AUX board A and B
DIP switch settings. See Tables 10 and 11 for a list of inputs and
outputs for the AUX boards.
Fig. 20 — AUX Board
Table 10 — AUX Board A Inputs and Outputs
Table 11 — AUX Board B Inputs and Outputs
NOTE: Fan A and B stage outputs are only used on STANDARD TIER
units, identified by the 10th position in the model number. Position 10 is
S and Position 13 is -, 1, 3, or 5.
1
2
3
4
5
6
7
8
ON
100K
100K
100K
CH1
CH2 CH3
CH4 CH5 CH6 CH7 CH8
TR1 TR2 TR3 TR4 TR5 TR6 TR7 TR8
STAT US SIO (LEN)
24 VAC
CH13 CH14
J9
J1
CH9
CH10
CH11
CH12
JP2
C61
CH13
D12
JP1
L3
L5
U21
L2
D6
D5
Q5
Y1
D7
D8
S1
D3
U1
Q1
U5
U6
U7
U8
U9
Q10
Q11
U10
J4
J3
J2
U4
U2
Q12
Q60
3 2 1
– G +
3 2 1
– G +
DIP SWITCH
J5
J6
J7 J8
RED LED - STAT US
GREEN LED - LEN
(Local Equipment Network)
JUMPER JP2 - "P"
JUMPER JP1 - "T"
Table 9 — AUX Board A and B DIP Switch Settings
AUX BOARD A DIP SWITCH 12345678
Address ON ON OFF OFF ON OFF ON OFF
AUX BOARD BDIP SWITCH 12345678
Address OFF OFF ON OFF ON OFF ON OFF
CHANNEL IN/OUT TYPE BOARD CONNECTOR CCN POINT DESCRIPTION (SEE NOTE)
CH 1 DO
J2
FC1_A Fan A Stage 1
CH 2 DO FC2_A Fan A Stage 2
CH 3 DO FC3_A Fan A Stage 3
CH 4 DO FC4_A Fan A Stage 4
CH 5 DO
J3
FC5_A Fan A Stage 5
CH 6 DO FC6_A Fan A Stage 6
CH 7 DO FC7_A Fan A Stage 7
CH 8 DO FC8_A Fan A Stage 8
CH 9 AO J4 CAPT010A % Capacity Circuit A (0-10 Vdc)
CH 10 AO J5 Not Used
CH 11 AI
J6
DGT_A Discharge Gas Temperature Circuit A
CH 12 AI SUCT_A Suction Gas Temperature Circuit A
CH 13 AI J7 LIQ_T_A Liquid Temperature Circuit A
CH 14 AI J8 LIQ_P_A Liquid Pressure Circuit A
CHANNEL IN/OUT TYPE BOARD CONNECTOR CCN POINT DESCRIPTION (SEE NOTE)
CH 1 DO
J2
FC1_B Fan B Stage 1
CH 2 DO FC2_B Fan B Stage 2
CH 3 DO FC3_B Fan B Stage 3
CH 4 DO FC4_B Fan B Stage 4
CH 5 DO
J3
FC5_B Fan B Stage 5
CH 6 DO FC6_B Fan B Stage 6
CH 7 DO FC7_B Fan B Stage 7
CH 8 DO FC8_B Fan B Stage 8
CH 9 AO J4 CAPT010B % Capacity Circuit B (0-10 Vdc)
CH 10 AO J5 Not Used
CH 11 AI
J6
DGT_B Discharge Gas Temperature Circuit B
CH 12 AI SUCT_B Suction Gas Temperature Circuit B
CH 13 AI J7 LIQ_T_B Liquid Temperature Circuit B
CH 14 AI J8 LIQ_P_B Liquid Pressure Circuit B

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier AquaForce 30XV400 and is the answer not in the manual?

Carrier AquaForce 30XV400 Specifications

General IconGeneral
BrandCarrier
ModelAquaForce 30XV400
CategoryChiller
LanguageEnglish

Related product manuals