EasyManuals Logo
Home>ComAp>Controller>InteliDrive Lite

ComAp InteliDrive Lite User Manual

ComAp InteliDrive Lite
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
ID–Lite-2.0 User guide, ©ComAp January 2011 50
ID-Lite-2.0 User guide.pdf
Starter
The closed relay energizes the starter motor.
The relay opens if:
the firing speed is reached or
maximum time of cranking is exceeded or
request to stop comes up
Fuel solenoid
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
EMERGENCY STOP comes or
Cooled engine is stopped or
in pause between repeated starts
Stop solenoid
The closed output energizes stop solenoid to stop the engine.
The output is active at least for Stop time, if the stop lasts longer; it stays active until all symptoms say
the engine is stopped.
The engine is stopped if:
RPM < 2 and
Oil pressure < Engine params: StartingPoil.
Hint:
The engine can be started anytime, if all symptoms say the engine is steady regardless of the fact the
Stop solenoid can still be active (in that case it is deactivated before cranking).
Stop Pulse
Output is active for 1 second after Stop solenoid output activation. This signal is sent to ECU in case
of engine stop request.
Ignition
The output closes after reaching value of CrankRPM, fixed 30RPM. Opens after stopping of the
engine or in pause during repeated start.
Prestart
The output closes prior to the engine start (Prestart) and opens when Starting RPM speed is reached.
During repeated crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
Preglow
The output closes prior to the engine start and opens when Starting RPM speed is reached. During
repeated crank attempts the output is closed too.
The output could be used for pre-glow or pre-heat.
Cooling pump
The output closes when engine starts and opens Engine params: AfterCool time after stop of the
engine.
Idle/Nominal
The output either follows the Nominal/Idle binary input in MAN mode or follows the engine state in
AUT mode:
The output Idle/Nominal closes after the timer Idle time elapses. The Idle time counter starts to
countdown when Start speed reached. The Underspeed protection is not evaluated during idle period.
A Start fail protection occurs if the RPM drop below 2RPM during idle state.
Air valves
Output closes together with Prestart and opens after the engine is stopped.

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals