ID–Lite-2.0 User guide, ©ComAp – January 2011 73
ID-Lite-2.0 User guide.pdf
Range: -1000 – +1000
AIO module
AnlInAIO1..4 lev1 [ ]
The level for AIO ANALOG INPUT 1..4 alarm detection.
Step: 1
Range: -100 - +10000
AnlInAIO1..4 lev2 [ ]
The level for AIO ANALOG INPUT 1..4 alarm detection.
Step: 1
Range: -100 - +10000
AnlInAIO1..4 del [s]
Delay for AIO ANALOG INPUT 1..4 alarm.
Step: 1 s
Range: 0 - 180 s
Hint:
Plug-in analog inputs protection alarms can be configured following way
Configuration Protection
Under Protection is activated only when measured value is under measured level.
Over Protection is activated only when measured value is over measured level.
Under+fls Level 2 protection is activated by sensor fail as well.
Over+fls Level 2 protection is activated by sensor fail as well.
SMS/E-Mail
Remote alarm messaging
If a GSM modem and/or Internet bridge is connected to the controller, the controller can send SMS
messages and/or emails in the moment when a new alarm appears in the Alarm list. The message will
contain a copy of the Alarm list.
To enable this function, you should select with setpoints Yel Alarm Msg and Red Alarm Msg, which
levels of alarms shall be announced (red/yellow/both) and also enter valid GSM phone number and/or
e-mail address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is possible to put either a
GSM number or e-mail to both setpoints.
NOTE:
An internet module must be available for sending of e-mails. Similarly, a GSM modem is necessary for
sending of SMS.
Hint:
There are 5 attempts for any active call (SMS/E-Mail). Timeout for connection is 90 sec and after 120
sec controller starts the next attempt. During the time the IL-NT is trying to send an active call type,
incoming calls are blocked.
Yel Alarm Msg [ OFF / ON ]
Set this setpoint to YES if you want to get messages when a yellow (warning) alarm occurs.
Hint
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)