ID–Lite-2.0 User guide, ©ComAp – January 2011 59
ID-Lite-2.0 User guide.pdf
SMTP UserPass
User password of e-mail account for verification of e-mail sender on SMTP server. If parameter left
empty, no verification is expected. Works for IB-Lite only.
SMTP Server IP
IP address of SMTP server. Works for IB-Lite only.
Contr MailBox
E-mail address used as “Sender” of alarm e-mails from IB-Lite.
Hint:
If SMTP server requires verification of sender, e-mail address has to be registered to SMTP server
and setpoints “SMTP UserName” and “SMTP UserPass” has to be set to correct values.
Time Zone
List of time zones used for time reference.
DNS IP Address
IP address of Domain Name Server.
Engine params
Starting RPM [RPM]
“Firing” speed when ID-Lite controller stops cranking (starter goes OFF).
Sd Underspeed protection is activated when RPM drops back below the Starting RPM for more than 5
second the engine starting procedure.
Limit is ignored when Gear teeth = 0 i.e. in engine operation without speed pickup (running state is
indicated from D+ or Starting POil.
Step: 1 RPM
Range: 5 – 1500 RPM
RPM meas fail indication
When during "Cranking state" ... i.e. Starter (or J1939 Start command) is activated
then one running condition was detected (D+ was activated or (POil > Starting POil) condition was
filled) - i.e. Starter was switched off based on it
and
within time of minimum of (fix 5s and Cranking time) do not appear RPM > Starting RPM --- then is
activate RPM meas fail.
Starting POil [Bar]
Controller stops cranking (starter goes OFF) when Oil Pressure (typically measured on AIN1) is over
Starting POil.
Step: 0,1 Bar
Range: 0,0 – 10,0 Bar
Hint:
There are three conditions for stop cranking: Starting RPM (just in case the Gear teeth > 0),
StartingPOil and D+ (when enabled). Starter goes off when any of these conditions is valid.
Prestart time [s]
Time of the PRESTART output closed prior to the engine start – i.e. before the binary outputs Fuel
solenoid and Starter are closed and opens when Starting RPM speed is reached. Set to zero if you
want to leave the output PRE-START opened.
Step: 1s
Range: 0 – 600 s