ID–Lite-2.0 User guide, ©ComAp – January 2011 46
ID-Lite-2.0 User guide.pdf
Inputs and outputs
Hint:
Any Binary input or output can be configured to any ID-Lite controller terminal or changed to different
function by LiteEdit (3.0 or higher) software. There is fix 1 sec delay when any binary input is
configured as protection.
Binary inputs ID-Lite - default
BI1 Rem start/stop
BI2 Access lock
BI3 Emergency stop
BI4 Remote OFF
BI5 Sprinkler
BI6 RemControlLock
Binary inputs – list
Not used
Binary input has no function. Use this configuration when Binary input is not connected.
Alarm
If the input is closed (or opened) selected alarm is activated.
Binary Alarm configuration items
Name 14 characters ASCII string
NC Normally closed Contact type
NO Normally opened
Warning Alarm type
Shut down
All the time Alarm active
Engine running only
Rem start/stop
External request for engine run. AUT mode only.
Emergency stop
If the input is opened, shut down is immediately activated. Input is inverted (normally closed) in default
configuration.
Hint:
In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured. To
back-up the Emergency stop function it is recommended to connect separate circuit for disconnection
of Fuel solenoid and Starter signals.
Sprinkler
If the input is closed all alarms are disabled except the binary input EMERGENCY STOP and "engine
overspeed protection".