all ID-Lite alarms are detected,
ID-Lite front panel RED LED blinks or lights,
Alarm is recorded on the ID-Lite alarm list screen,
BUT engine remains running.
Hint:
Warning SprinklActive is indicated in the Alarm list if sprinkler mode active to inform the operator that
the engine is not protected.
Access lock
If the input is closed, no setpoints can be adjusted from controller front panel and engine mode (OFF-
MAN-AUT) cannot be changed.
Hint:
Access lock does not protect setpoints and mode changing from LiteEdit. To avoid unqualified
changes the selected setpoints can be password protected.
Remote OFF
If closed, InteliDrive-Lite is switched to OFF mode (there are three modes OFF-MAN-AUT). When
opens controller is switched back to previous mode.
Hint:
This binary input should be connected to schedule timer switch, to avoid start of engine.
Remote MAN
If the input is active, MAN mode is forced to the controller independently on the position of the MODE
selector.
Remote AUT
If the input is active, AUT mode is forced to the controller independently on the position of the MODE
selector. If another of „remote inputs is active, then the REMOTE AUT input has the lowest priority.
RemControlLock
If the input is active, setpoints writing or command sending from the external terminal is disabled.
Emergency manual
If the input is activated the controller behaves like when switched to OFF mode and opens all binary
outputs. There is one exception STOP SOLENOID doesnt activate on this transition.
Detection of "running" engine and subsequent alarm message "Sd Stop fail" is blocked.
The controller shows “Emerg Man state and the engine can not be started.
After the input is open again, the controller recovers to previous state and behaves according to the
actual situation.
Function is active in any controller mode.
StartButton
Binary input has the same function as Start button on the ID-Lite front panel. It is active in MAN mode
only.
StopButton
Binary input has the same function as Stop button on the ID-Lite front panel. It is active in MAN mode
only.
FaultResButton
Binary input has the same function as Fault reset button on the ID-Lite front panel.

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals