Regulator
LBI Speed Up
LBI Speed Down
AOUT
OutChar
InpChar
LAI SpdRequest [ OFF, CU:AI1, CU:AI2, CU:AI3
AIO: IA1, AIO: AI2, AIO: AI3, AIO: AI4 ]
Selection of analog Speed request in controller MAN mode.
OFF: Speed request selection is done by binary inputs.
CU: AI1, CU: AI2, CU: AI3: AIO1 … AIO4: Speed request via analog input only. Binary inputs are
ignored. Analog speed request is ignored in AUT mode.
Reg Input [CU: AI1, CU: AI2, CU: AI3,
AIO: IA1, AIO: AI2, AIO: AI3, AIO: AI4, RPM-BI3 ]
PI loop analog input selection or from central unit (CU) or from plug-in (AIO). The Speed request
(regulator output) is set to Reg Bias value in the case of selected analog input sensor fail.
Reg Bias [ - ]
Constant PI regulator output when the LBI R Reg Disable = closed.
Step: 1
Range: 0 – 10000
Default: 0
Request 1 [ - ]
Regulator requested value.
Step: 1
Range: -10000 – +10000
Default: 0
Request 2 [ - ]
Regulator requested value when LBI Request2 is active.
Step: 1
Range: -10000 – +10000
Default: 0
Reg Gain [ % ]
Regulator gain.
Step: 0,1