InteliPro, SW version 1.4, ©ComAp – April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
Transistor, switching to negative supply terminal
500mA (suppression diodes required for inductive loads)
Predefined: VDO 10Bar, VDO Temperature, VDO Fuel level
User defined: 10 points non-linear sensors can be defined by the
user
3ph mains voltage, 3ph mains current
1% of nominal voltage at20°Cand50or60Hz1,5%onthe
complete frequency and temperature range
2% of nominal current at CT Ratio = 50A / 5A or higher
30-70Hz, measured from L3
CAUTION!
To assure accurate measurement of the mains current, we recommend direct metallic connection
between COM terminal of Mains Current measurement and the minus "-" terminal of the unit power
supply. The potential difference between those two points must not overreach 10 V.
NVD and Sync Check measurement
NVD: 277V
Sync Check: 480 V